1-805-484-2992

Quotes - Engineering - Sales

AT75P

Mueller
Product Style Ratings Configuration
Heat Exchanger Plate & Frame 350 PSI / 410°F B Frame
AT75P datasheet Download Datasheet

Note: the unit pictured is representative of the standard build and may not exactly depict p/n AT75P as shown on this page.

Mueller AT75P

AT75P specifications

Description

AT75P is the P-series plate configuration of the Mueller Accu-Therm AT75 frame. It is a distinct part from the base AT75: the frame and port geometry are shared, but the plate pressing is not, so a P plate and a base plate are not interchangeable in a pack and their gaskets differ. The P plate is Mueller's high-pressure pressing, listed in the Accu-Therm I&O manual plate-code table. It carries a deeper draw and heavier support pattern than the base plate, which raises the differential pressure the pack will hold at the cost of a slightly higher pressure drop. Frame geometry is unchanged - 75-5/8" by 25-1/2" plates on 6" ports, packs from 34-5/8" - 160-5/8", roughly 120 - 2,900 sq ft of surface at about 4.3 square feet per plate, and water flow to 1800 GPM. Gaskets attach by the Clip-In method. Frame styles offered: B Frame - for larger units, plates hang from the upper guide bar; capacity to 900 plates. If you are matching a nameplate, the series letter is part of the part number and needs to carry through to any plate or gasket order.

Product Overview

Part Number:
AT75P
Series:
Accu-Therm
Brand:
Mueller
Codes & Compliance:
ASME Sec VIII Div 1, CRN, DNV
Also Written:
AT 75P, AT-75P, AT75 P, AT75-P

Configuration & Size

Surface Area (Sq/Ft):
120 - 2,900 sq ft
Connection Type:
Studded port standard; lap-joint, weld-neck, ferrule, Victaulic
Frame Type:
B | B Frame (Beam)
Max Plate Count:
670 (est.)
Mounting:
Floor mounted frame
Passes:
Single pass standard; multi-pass available
Plate Height:
75-5/8"
Plate Pack Length Range:
34-5/8" - 160-5/8"
Plate Pattern:
P series, chevron H / V
Plate Thickness:
0.5 mm standard
Plate Width:
25-1/2"
Port Size:
6"
Wall Construction:
Single wall gasketed
Heat Transfer Area per Plate (Sq/Ft):
4.3 (est.)
Max Flow Rate (GPM):
1800
Performance Rating:
U-value 1,500 BTU/hr-ft²-°F and greater
Performance Rating (Basis):
Clean water-to-water service; 1F to 3F approach. Actual duty depends on plate count, pattern, and fluid properties.

Materials of Construction

  • Frame: Painted carbon steel; stainless optional. Zinc-plated compression bolts
  • Gasket: NBR or EPDM standard; High-Temp EPDM, Viton/FKM, Butyl. FDA/3-A
  • Gasket Attachment: Clip-In
  • Plate: 316 SS standard; 304 SS, Titanium, Hastelloy C-276, SMO 254 optional

Rating

  • Max Temperature: 410°F design; 302°F - 329°F gasket limit
  • Max Working Pressure: 350 PSI design (high-pressure plate)
  • Min Temperature: -20°F (MDMT 32°F typical)
  • Test Pressure: 1.3 x MAWP

Quote Request Form:

Questions?

1-805-484-2992